If you’ve ever worked as a Lightning Arrester Tester, or spent time on a power substation floor troubleshooting performance issues or verifying equipment reliability, you’ve probably encountered confusion around leakage current and resistive current tests. At my role leading a team that designs and distributes testing tools for electrical infrastructure—including high-voltage surge arresters that keep grid components safe from lightning strikes—this question comes up at least a few times a week. New field technicians might mix up the two terms, even some veteran operators will use them interchangeably when they don’t fully grasp how each test delivers critical, different data. Let’s break this down with real-world context, since this isn’t just a theoretical distinction—it impacts how you maintain grid reliability, avoid unplanned outages, and spot failing equipment before it causes costly damage. Lightning Arrester Tester

First, let’s ground both terms in what a lightning arrester actually does, because if you understand the arrester’s core function, the purpose of each test will click into place. A lightning arrester is a protective device installed on transmission lines, transformers, and circuit breakers that sits in parallel with the high-voltage line it’s guarding. Its job is simple when it works: under normal grid operating voltage, it acts like an insulator—no current flows through it. When a surge (from lightning, a grid switch, or a voltage spike) hits, it becomes a conductor, diverting that dangerous surge current to the ground to protect connected equipment. After the surge passes, it snaps back to acting as an insulator, so normal power flow resumes.
Over time, though, arresters degrade. Moisture seeps into their housing, their internal varistors (voltage-dependent resistors made of metal oxide, typically zinc oxide) develop cracks, or surface contamination builds up. This degradation changes how they behave even at normal operating voltage, which is where our two tests come in.
Let’s start with leakage current, because it’s the older, more widely known test, and it’s often the entry point for new technicians. Leakage current is the total amount of small, continuous current that flows through the arrester when it’s operating at its normal, continuous AC voltage. To put this in perspective: normal leakage current for a medium-voltage arrester might be measured in microamps (µA), like 50 to 200 µA, while a failed arrester could have leakage current in the milliamp (mA) range—thousands of times higher. That’s a huge red flag. But here’s the key limitation of leakage current: it doesn’t distinguish between where that current is flowing. The total leakage current is a combination of two components: capacitive current, which flows through the insulation material of the arrester, and resistive current, which flows through the varistor core. Capacitive current is constant for an arrester at a given voltage—its job is just to offset the small reactive properties of the insulation. The resistive current is the bad guy; that’s the current that comes through the degraded varistor, the water, or the contamination, because those are resistive pathways.
Here’s a real example from last year that still sticks with me. We had a client in the Midwest who was running annual leakage current tests on their 138 kV arresters, and all their readings were within the “normal” range—no higher than 180 µA, so they marked all units as good. Six months later, one of those arresters failed, taking a transformer offline and costing them an estimated $200,000 in lost power and emergency repairs. When our team went to test the remaining arresters, we found that two had resistive current levels 10 times higher than threshold, even though their total leakage current was identical to the units they’d marked as good. The problem? The leakage current test only told part of the story. The capacitive component in the two failed units was lower, but the resistive component was through the roof, so the total number looked normal. That’s the gap resistive current tests were built to fill.
Now, resistive current (sometimes called resistive leakage current) is exactly what it sounds like: it isolates only the resistive component of that total leakage current, stripping out the capacitive current noise to give you a clear reading of how much bad current is flowing through the conductive pathways in the arrester. That’s the critical difference. Leakage current is total current; resistive current is the problematic, current that directly indicates the arrester’s internal health.
But let’s dive deeper into how each test is performed, because the process also highlights their differences. Leakage current tests are straightforward: you connect your test instrument (like our standard Lightning Arrester Leakage Current Tester) across the arrester’s terminals, apply the full normal operating voltage of the arrester, and measure the total current that flows from line to ground. It’s fast, takes 10 minutes per unit, and is perfect for quick, high-volume screening. You can test dozens of arresters in a day, which makes it ideal for annual or semi-annual grid-wide surveys.
Resistive current tests, though, are a bit more involved—you need a specialized tool that can separate the two components of the current, which requires measuring not just current amplitude, but phase angle too. Capacitive current leads the applied voltage by 90 degrees, while resistive current is in phase with the voltage. By measuring the phase difference between the applied AC voltage and the current through the arrester, the test instrument can mathematically subtract the capacitive component, leaving you with just the resistive current. For field use, that means you need a more sophisticated tester—like our Lightning Arrester Resistive Current Analyzer, which syncs directly with the grid’s voltage waveform to get accurate phase data in real time. This test takes a bit longer, around 15 to 20 minutes per unit, but it delivers far more actionable data.
Let’s talk about when to use each test, because that’s where a lot of technicians still go wrong. If you’re doing a first pass of 50 arresters to weed out obvious failures (like a unit with total leakage current of 5 mA, which is definitely bad), leakage current is perfect. It’s fast, it’s simple, and it catches the most severe, obvious failures. But if you’re doing predictive maintenance—spotting degradation before it leads to a failure—resistive current is non-negotiable. The Midwest client’s mistake was relying solely on leakage current for predictive data. Resistive current readings don’t have a vague “normal” range the way total leakage current does; most utilities set a threshold of 200 µA (or sometimes 10% of the arrester’s initial baseline reading, whichever is lower) for resistive current. If that threshold is crossed, you know there’s internal damage—moisture intrusion, varistor breakdown, contamination— that’s going to get worse over time, leading to an eventual failure.
Another common misconception: some techs think that once you do a resistive current test, you don’t need to do leakage current at all. That’s not true either. Baseline leakage current is important to track over time, because a sudden spike in total leakage current (even if resistive current is still under threshold) can indicate an issue with the arrester’s surface insulation, like a layer of salt or dust buildup that’s affecting performance, even if the core is still good. In that case, cleaning the arrester might fix the leakage current, whereas a resistive current spike would signal you need to replace the unit.
Let’s cover a third example to drive this home. Last quarter, we worked with a utility in the Pacific Northwest that has a coastal grid, so their arresters are exposed to constant salt spray, which causes surface contamination. They were doing monthly leakage current tests, and most units had a consistent 120 µA total leakage current. One unit recently jumped to 250 µA, so they pulled it for a resistive current test. The resistive current came back at only 80 µA, well under threshold. That told us the problem wasn’t internal degradation—it was surface salt contamination. They just cleaned the arrester, and the leakage current dropped back to 125 µA. If they had relied on resistive current alone, they might have unnecessarily replaced a perfectly good unit, wasting thousands of dollars. That’s why both tests have a place in a proper maintenance program: leakage current catches external surface issues, resistive current catches internal core issues.
Now, let’s address a question I get all the time: why don’t all utilities just do resistive current tests instead of leakage current? The answer comes down to cost and practicality. A high-quality resistive current tester costs two to three times more than a standard leakage current tester, and it requires more training to use correctly. A new technician can pick up a leakage current tester, follow the manual, and get a valid reading in 10 minutes. To get an accurate resistive current reading, you have to make sure the test leads are properly shielded, that there’s no stray current from nearby equipment interfering, and that you sync the instrument correctly with the grid’s voltage—all things that take practice. For smaller utilities with limited budgets and small maintenance teams, leakage current is still the go-to for routine checks, as long as they understand its limitations.
Another key point: international standards back this up. IEC 60099-5, the global standard for surge arrester maintenance, recommends that leakage current testing be performed at regular intervals, and that resistive current testing be used to further analyze any readings that fall outside normal ranges. The standard makes it clear that total leakage current is a screening tool, while resistive current is the diagnostic tool for assessing arrester health. That’s not just my opinion— that’s the guidance from the body that sets global electrical safety standards.
I’ve spent the last 15 years working with power grid operators, designing testing equipment to make these jobs easier, and I can tell you that the biggest cause of unnecessary arrester failures is misinterpreting these two tests. I’ve seen teams replace perfectly good arresters because they thought a resistive current spike in a single phase meant all three phases were bad, or they missed a failing unit because they only looked at resistive current and didn’t check leakage for surface contamination. The line between these two tests is small, but it’s critical.
Let’s recap to make sure this is clear, in a way that you can reference in the field:
- Purpose: Leakage current measures total current through the arrester, used for quick screening. Resistive current isolates the problematic current in the varistor core, used for diagnostic predictive maintenance.
- What they measure: Leakage = capacitive current (constant, insulation-related) + resistive current (degradation-related). Resistive current is only the degradation-related current.
- Use cases: Leakage for high-volume initial checks and surface contamination flags. Resistive for catching internal degradation and planning replacements.
- Tools and training: Leakage current testers are lower cost, simpler to use. Resistive current testers are more complex, require waveform sync and phase analysis, higher cost.
If you’re still confused about which test to use for your specific setup, or if you’re upgrading your testing equipment to get more reliable data, our team has supported hundreds of utilities in choosing the right tools for their needs. We work with teams from small rural co-ops to large transmission system operators, helping them balance cost, speed, and accuracy in their maintenance programs.
Whether you’re just starting out as a Lightning Arrester Tester or you’ve been in the field for decades, the distinction between leakage and resistive current tests isn’t just a technical detail—it’s the difference between a routine maintenance check and a costly unplanned outage. If you’re looking to upgrade your testing equipment, verify your current test procedures, or just get a second opinion on interpreting readings, our team is here to help. We work closely with field technicians to understand their challenges and provide tailored solutions that fit their specific grid needs.

For more information on our range of Lightning Arrester testing equipment and to discuss your maintenance requirements, we encourage you to reach out to our team for a consultation. We’re here to support you in keeping your grid safe and reliable.
Power Quality Analyzer References:
- International Electrotechnical Commission. IEC 60099-5: Surge arresters – Part 5: Selection and application recommendations for surge arresters for AC systems
- IEEE Power & Energy Society. IEEE Std C62.22: Guide for the application of metal-oxide surge arresters for AC power systems
- Sima, W., Yuan, T., & Chen, W. (2018). Condition monitoring of metal-oxide surge arresters: A review of methods and technologies. IEEE Transactions on Power Delivery, Vol. 33, No. 4, pp. 1972-1982.
Refine On (Hebei) Electric Power Technology Co., Ltd.
Refine On (Hebei) Electric Power Technology Co., Ltd. is one of the most reliable lightning arrester tester manufacturers and suppliers in China, also supports customized service. Please feel free to wholesale advanced lightning arrester tester at competitive price from our factory. Contact us for quotation.
Address: Building 13, Liandong U Valley, No.64, Jing SAN South Street, Economic Development Zone, Mancheng District, Baoding City, China
E-mail: wang@transformer-test.com
WebSite: https://www.transformer-test.com/